When the fan leaves the factory, it is divided into six parts: collector, first-level fan, second-level fan, diffuser, square joint and diffusion tower. In order to manufacture and transport conveniently, the diffuser is often divided into two sections:
1. Handle the installation site according to the fan specifications, and ensure that there is enough space in the site so that the extracted wind can be discharged into the atmosphere smoothly (the harmful gas must not be directly discharged into the atmosphere). The floor of the machine base must be flat and tamped, and steel rails must be laid.
2. The fan must be installed at the outlet of the air shaft of the coal mine, and ensure that the ventilation pipe of the isolation cavity is open to the atmosphere. Set up embedded parts at the joint of the negative machine and the roadway to fix the joint of the roadway. An explosion-proof door must be installed at the mouth of the air shaft.
3. Before installation, all parts of the fan must be checked: a. Whether the mechanical parts are complete; b. Whether the impeller rotates flexibly; c. Whether the blades and the barrel wall are friction; d. Whether the blades are installed firmly; e. Whether the blades are damaged . If problems are discovered, they must be dealt with in a timely manner, and hidden dangers of accidents must not be allowed.
4. During installation, hoist the components of the fan to the laid steel rails in order, pad the sealing ring where needed, connect the components firmly with bolts, and connect the power cord and the temperature measuring instrument cord according to the motor manual.
5. Check whether the oil inlet and outlet channels are unobstructed, and inject No. 2 molybdenum disulfide lithium-based lubricant (or grease with better quality).
6. Check all parts, after the installation is correct, the manual brake is correct, and then the trial operation can be carried out.
7. For motors that have undergone long-distance power transmission or have been left unused for a long time, the stator insulation resistance must be measured before use (insulation resistance shall not be less than 0.5 ohm 380V), and the power supply can be turned on and the fan can be started after passing the inspection. Always observe the current, voltage, motor stator and bearing temperature during trial operation.